Abstract
The paper presents an incremental development of the methodology for chilled water system design
optimization. Initially, the system configuration parameters are varied with fixed design conditions
to confirm the established best practice design criteria, followed by a comprehensive system design
optimization. The implemented simulation-based optimization approach couples the Dymola/Modelica
dynamic modeling and simulation program with GenOpt generic optimization program to find optimal
system configuration. A dynamic system model is developed to vary and simulate different chilled water
system configurations. Optimization of the chilled water system is achieved at both design and configuration
level using five design variables. Two discrete variables are related to system configuration: number
of chillers and number of cooling towers and three continuous variables are related to system design:
building load demand, temperature difference across condenser, and cooling tower fan speed. The strategy
of varying system design and configuration variables together for overall system optimization proved
to be the most energy efficient. For a fixed building load demand, power consumption of the considered
system can be reduced 17-43% by selecting an optimal system configuration.