Abstract
We are aiming to develop a high temperature heat pump using R1233zde as refrigerant by using an ejector as work recovery measure instead of an expansion valve. Based on the design condition at 50°C source and 130°C sink temperature and about 70kW heating capacity, we show that the ejector efficiency can remain within acceptable limits even under deviating operating conditions by using a variable bypass instead of a rigid ejector geometry. The ejector efficiency can thus be kept high from about 30% in the design condition over a wide operating range. The COP increase compared to a conventional refrigeration circuit is approx. 30% in the design condition.
| Original language | English |
|---|---|
| Title of host publication | 4th High-temperature Heat Pump Symposium: Book of Presentations |
| Publication status | Published - 2024 |
| Event | High Temperature Heat Pump Symposium 2024 - Kopenhagen, Denmark Duration: 23 Jan 2024 → 24 Jan 2024 https://www.hthp-symposium.org/hthp-symposium-2024/ |
Conference
| Conference | High Temperature Heat Pump Symposium 2024 |
|---|---|
| Country/Territory | Denmark |
| City | Kopenhagen |
| Period | 23/01/24 → 24/01/24 |
| Internet address |
Research Field
- Efficiency in Industrial Processes and Systems
Fingerprint
Dive into the research topics of 'Design and off-design performance of a high temperature heat pump with ejector'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver